NOR01(B)-FIRE
ACCESS CONTROL ACCESSORIES
FIRE RATED PRODUCTS
NOR 01(B)-FIRE Unmonitored Mini Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe
UK FIRE TESTED
DOORS BS EN1634:1 FD30 & FD60
BS EN1634:1
Power Supply
+
250
+
11
6
JP1
42
180
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
26
38
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .
NOR0 1 (B) Unmonitored Mini Magnet
• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe
Power Supply
+
250
+
11
6
JP1
42
180
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
26
38
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .
All dimensions in mm
NOR01 EXTP Extended Top Plate for Mini Magnet
• Anodised Aluminium
NOR 1A-12VL Power Supply • 220Vac power input • 12Vdc 1Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 305 304 85
NOR 1A-12VS Smallbox Power Supply • 220Vac power input • 12Vdc 1Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 225 195 80
NOR 1A- 24 VL Power Supply • 220Vac power input • 24 Vdc 1Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 305 304 85
FIRE RATED PRODUCTS
NOR02 (B)-FIRE Monitored Mini Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe • Status LED ● Red ● Green
UK FIRE TESTED
DOORS BS EN1634:1 FD30 & FD60
BS EN1634:1
Power Supply
Contact
+
250
+
N.O.
N.C.
C
11
6
JP1
42
180
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
26
38
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output
door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .
NOR02(B) Monitored Mini Magnet
• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe • Status LED ● Red ● Green
Power Supply
Contact
+
250
+
N.O.
N.C.
C
11
6
JP1
42
180
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
26
38
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output
door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .
All dimensions in mm
NOR02 DS (B) Monitored Mini Magnet With Door Status
• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Door Status Monitoring • Lock Monitoring
• Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe • Status LED ● Red ● Green
Power Supply
Contact
Contact
+
250
+
N.O.
N.O.
C
N.C.
C
11
6
JP1
42
190
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
26
38
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output
door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .
All dimensions in mm
NOR 2 A- 12 VL Power Supply • 220Vac power input • 12 Vdc 2 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 305 304 85
NOR 2 A-12VS Smallbox Power Supply • 220Vac power input • 12Vdc 2 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 225 195 80
NOR 003N Plastic Cover
• Clear plastic cover • For break-glass unit
All dimensions in mm
Setting the Standard
NOR 3 A- 12 VL Power Supply • 220Vac power input • 12 Vdc 3 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 305 304 85
NOR 3 A-12VS Smallbox Power Supply • 220Vac power input • 12Vdc 3 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 225 195 80
NOR 3 A- 24 VL Power Supply • 220Vac power input • 24 Vdc 3 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 305 304 85
NOR 004F -PTE Exit Button
• Brushed Stainless Steel •
Green dome button
• Flush mount • FREE : Add your company logo • COM-N/O COM-N/C
OPTIONS
NOR- DRB-SH
NOR 004F-PTE PRESS TO EXIT
M22 x P1.5
2
85
35
29.9
5
85
23
Ø22
0.6 Thickness
45
Operating Travel 2.7
FREE POSITION
OPERATING POSITION
SPEC I F I CAT ION • Max. Rating: 5A/125/250 Vac. • Contact resistance: 50mΩ Max. (Initial) . • Operating travel: 2.7mm.
• Operating life (Mechanical) : Over 100,000 times. • Cables included.
All dimensions in mm
EXIT DEVICES
NOR 004S-PTE PRESS TO EXIT Exit Button
• Brushed Stainless Steel •
Green dome button
• Surface mount • FREE : Add your company logo • COM-N/O COM-N/C
M22 x P1.5
40
85
2
35
29.9
5
23
0.6 Thickness
85
Ø22
45
Operating Travel 2.7
FREE POSITION
OPERATING POSITION
SPEC I F I CAT ION • Max. Rating: 5A/125/250 Vac. • Contact resistance: 50mΩ Max. (Initial) • Operating travel: 2.7mm.
• Operating life (Mechanical) : Over 100,000 times. • Cables included.
NOR04(B) Unmonitored Double Mini Magnet
• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 2 x 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe
Power Supply
+
11
500
+
180
38
JP1
6
42
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
26
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 3.7kg (approx) .
All dimensions in mm
NOR0 5 (B) Monitored Double Mini Magnet
• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 2 x 600lbs (272Kg) • Electro-less Nickel Plated Armature • Status LED ● Red ● Green
Power Supply
Contact
+
11
500
+
N.O.
N.C.
C
180
38
JP1
6
42
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
26
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) .
• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Humidity: 0 ~ 95% non-condensing. • Weight: 3.7kg (approx) .
• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output-door closed) (SPDT rated 0.25A at 12Vdc) .
All dimensions in mm
NOR0 5 DS (B) Monitored Mini Magnet With Door Status
• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Door Status Monitoring • Lock Monitoring
• Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe • Status LED ● Red ● Green
Power Supply
Contact
Contact
+
11
500
+
N.O.
N.O.
C
N.C.
C
190
38
JP1
6
42
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
26
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output
door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .
All dimensions in mm
NOR 5 A- 12 VL Power Supply • 220Vac power input • 12 Vdc 5 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 305 304 85
NOR 5 A- 24 VL Power Supply • 220Vac power input • 24 Vdc 5 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit
SWITCH
H W D 305 304 85
NOR 008F-PTE PRESS TO EXIT
Exit Button
• Stainless Steel • Green finish • Raised green dome button • Flush mount • COM-N/O COM-N/C
M22 x P1.5
22 17.5
85
5
85
23
0.6 Thickness
Ø22
28.2
Operating Travel 2.7
FREE POSITION
OPERATING POSITION
SPEC I F I CAT ION • Max. Rating: 5A/125/250 Vac. • Contact resistance: 50mΩ Max. (Initial) . • Operating travel: 2.7mm.
• Operating life (Mechanical) : Over 100,000 times. • Cables included.
All dimensions in mm
Setting the Standard in Access Control
EXIT DEVICES
FIRE RATED PRODUCTS
NOR10(B)-FIRE Unmonitored Standard Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 1200lbs (544Kg) • Electro-less nickel plated armature
UK FIRE TESTED
DOORS BS EN1634:1 FD30 & FD60
BS EN1634:1
Power Supply
+
268
+
9
17
JP1
67
185
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
40
61
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 4.71kg (approx) .
NOR 10 (B) Unmonitored Standard Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 1200lbs (544Kg) • Electro-less nickel plated armature
Power Supply
+
268
+
9
17
JP1
67
185
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
40
61
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 4.71kg (approx) .
All dimensions in mm
NOR10 EXTP Extended Top Plate for Standard Magnet
• Anodised Aluminium
NOR12/24(B) External Magnet
• Operating voltage 12~24Vdc (Selectable) • Stainless Steel housing • Holding force up to 1200lbs (545Kg) • Weather resistant: IP67 • Sealed electronics
WEATHER RESISTANT − IP 67 −
STAINLESS STEEL
222
17
62
185
42
61
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) .
• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Humidity: 0 ~ 95% non-condensing. • Weight: 3.7kg (approx) .
• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output-door closed) (SPDT rated 0.25A at 12Vdc) .
188
NOR 014S-PTE Exit Button
• ABS Plastic • Legend: Press to Exit • • Surface mount • Weather resistant: IP65 • COM-N/O COM-N/C
Green dome button
WEATHER RESISTANT − IP 65 −
M22 x P1.5
2
35
29.9
85
5
23
0.6 Thickness
85
45
Operating Travel 2.7
40
FREE POSITION
OPERATING POSITION
SPEC I F I CAT ION • Max. Rating: 5A/125/250 Vac. • Contact resistance: 50mΩ Max. (Initial) • Operating travel: 2.7mm.
• Operating life (Mechanical) : Over 100,000 times. • Cables included.
NOR15 Breakglass Call Point
• Green plastic • Break glass • Surface mount
NOR 15 • Single pole
OPTIONS
NOR 15 N- Key (5)
NOR003N
Power Supply
+
+
+
85
Electromagnetic Locks (Locked)
51
Alarm
Y
GENC
EMER
EASE
RREL
85
DOO
E
SHER
PRES
Power Supply
+
+
+
Electromagnetic Locks (Unlocked)
Alarm
Spec i f i cat ion • COM / NO / NC Change-over-contacts x 2
• Contact resistance 150m • Contact resistance 3A @125V ac
FIRE RATED PRODUCTS
NOR 20 (B)-FIRE Monitored Standard Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 1200lbs (544Kg) • Electro-less nickel plated armature • Status LED ● Red ● Green
UK FIRE TESTED
DOORS BS EN1634:1 FD30 & FD60
BS EN1634:1
Power Supply
Contact
+
268
+
N.O.
N.C.
C
9
17
JP1
67
185
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
40
61
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output
door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 4.71kg (approx) .
NOR 20 (B) Monitored Standard Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 1200lbs (544Kg) • Electro-less nickel plated armature • Status LED ● Red ● Green
Power Supply
Contact
+
268
+
N.O.
N.C.
C
9
17
JP1
67
185
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
40
61
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output
door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 4.71kg (approx) .
All dimensions in mm
NOR21KEY-N(5) Key
• Black plastic key • For break-glass unit • Pack of 5
All dimensions in mm
Setting the Standard
NOR 21-N 2 POLE Breakglass Call Point
• Green plastic • Break glass • Surface mount
OPTIONS
NOR0 03-N
NOR 21N -Key(5)
88
Power Supply
60
+
+
+
Electromagnetic Locks (Locked)
Alarm
Y
GENC
EMER
EASE
RREL
88
DOO
E
SHER
PRES
Power Supply
+
Reset key
+
+
Switch 2
Switch 1
Electromagnetic Locks (Unlocked)
Alarm
SPEC I F I CAT ION • COM / NO / NC Change-over-contacts x 2
• Contact resistance 150m • Contact resistance 3A @125V ac
NOR 22-3- KEY Plastic Key • Clear plastic key • For External B reak- G lass U nit NOR-22-3WP
All dimensions in mm
Setting the Standard
NOR 22-3WP Waterproof Breakglass Call Point
• Green plastic • Triple pole • Resettable • Surface mount • Externally rated weatherproof • COM / NO / NC Change-over-contacts x 3
WEATHER RESISTANT − IP 67 −
H W D 135 125 62
All dimensions in mm All dimensions in
Setting the Standard in Access Control
134
EXIT DEVICES
NOR2 2 KEY-N(5) Key
• Black plastic key • For break-glass unit • Pack of 5
All dimensions in mm
Setting the Standard
NOR22N-EDR Resettable Call Point
• Green plastic • Resettable • Surface mount
OPTIONS
CP22-N Key
MXO03-N
88
Power Supply
60
+
+
+
Electromagnetic Locks (Locked)
Alarm
Y
GENC
EMER
EASE
RREL
88
DOO
E
SHER
PRES
Power Supply
+
Reset key
+
+
Switch 2
Switch 1
Electromagnetic Locks (Unlocked)
Alarm
SPEC I F I CAT ION • COM / NO / NC Change-over-contacts x 2
• Contact resistance 150m • Contact resistance 3A @125V ac
NOR 40DS (B) Double Standard Magnet
• Operating voltage 12~24Vdc (Selectable) • Holding force up to 2 X 1200lbs (544Kg) • Aluminium housing • Electroless nickel plated armature • Door status: An independent contact that works separately from the magnet to show door status not lock status • Status LED ● Red ● Green
MONITORED WITH DOOR STATUS
Power Supply
Contact
+
532
+
N.O.
N.C.
C
185
17
61
9
JP1
67
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
40
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output
door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight:9.3kg (approx) .
All dimensions in mm
Setting the Standard in Access Control
183
Electric Locking
EXIT DEVICES
DRB0 44S Series Budget Green Dome Button
• Brushed Stainless Steel Plate • Budget green dome button • Surface mount • COM-N/O COM-N/C • Supplied with security screws • Available in Green or Black Housing
Order Codes DRB044S-PTE ( GREEN)
50mm
40mm
All dimensions in mm
Safety straps available from Norbain for the Mini and Standard Magnets and the Mini and Standard Armatures, bringing an extra level of safety to our magnetic and Armature products. Safety Straps for Magnetic Locks Bringing extra safety to electric locking
MAG-55 Safety Strap.
Safety Straps for Standard or Mini Armatures
Safety Straps for Standard or Mini Armatures
All dimensions in mm
Setting the Standard in Access Control
AUDIO AND VIDEO ENTRY
NOR 60 (B) Unmonitored Double Standard Magnet
• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 2 x 1200lbs (544Kg) • Electro-less nickel plated armature
Power Supply
+
532
+
185
17
61
9
JP1
67
CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.
40
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .
• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight:9.3kg (approx) .
All dimensions in mm
Setting the Standard
NOR 165 Soleniod Bolt
• Operating voltage 12Vdc (24Vdc available to order) • Die-Cast Metal • Fail-Safe • Adjustable Timer • Monitored
JP3: Control ML-350 to be locked by door status.
It is applied to fail-safe mode only.
JP3: Power to lock without any devices.
SPEC I F I CAT ION • Voltage 12VDC . • Current draw: 570 mA at 12Vdc • Monitoring: N/C Contact
• Adjustable Timer 0~3 seconds . • Operational Door Gap 6mm Max • Bolt : 14mm throw, 12.7mm Diameter
All dimensions in mm
Setting the Standard in Access Control
Electric Locking
NOR 180 Electric Dropbolt
• Operating voltage 12~24Vdc • Stainless Steel • Fail-Safe (Power to Lock) • Vandal resistant • Built-in logical circuitry • Auto-relocking timer delay: 0, 3, 6 or 9 seconds
VANDAL RESISTANT
STAINLESS STEEL
16.5
Ø5.3xØ10.5 (2 Places)
30.8
Ø9.9
24
57.5
AUTO RELOCKING TIMER SETTINGS
45
20
Use jumpers to adjust the time between 0 to 9 seconds for door locking time delay. This is the time, which takes the dropbolt to automatically lock after the door is closed.
100 75
R8
210
149
185
R12.5
ON 1 2
ON 1 2
140
0 Seconds
3 Seconds
ON 1 2
1 2
ON
6 Seconds
9 Seconds
3
30.2
12.5
25
41
10
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: Pull in 0.9A, Holding 0.3A at 12Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 45°C (14 to 131°F) .
• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Magnetic bolt status output indicates bolt locked or unlocked status (SPDT rated 3A at 30Vdc) .
• Humidity: 0 ~ 95% non-condensing. • Horizontal or vertical installation. • Face plate material: Stainless Steel.
• Tested to 500,000 cycles. • Weight: 0.6kg (approx) .
All dimensions in mm
Setting the Standard in Access Control
Electric Locking
NOR 200 UNMONITORED
Shear Magnet
• Operating voltage 12~24Vdc • Holding force up to 1500lbs (680Kg) in shear
30
182
182
48
48
GS200-SH
GS200-GH
14
180
35
180
164
164
VOLTAGE SELECTION JUMPERS
MAGNET BOND SENSOR OUTPUT
N.C. output while door is unlocked; N.O. output while door is locked by the electromagnetic lock
Check jumper settings before connecting the lock to 24VDC input power. Damage to the lock may result from incorrect jumper settings.
N.C.
N.O. COM
Control Device N.C. Contactor or Access relay
27
33
Power Input SPDT relay
3A@30VDC
+ −
+ −
Power Supply
43
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 500mA at 12Vdc, 250mA at 24Vdc (at temperature 20°C) . • Operating temperature: -30 ~ 55°C (-22 to 131°F) .
• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output-door closed) (GS-200M) (SPDT rated 3A at 30Vdc) .
• Humidity: 0 ~ 95% non-condensing. • Special Zinc finish for magnet and armature plate. • Weight: 2.0kg (approx) .
All dimensions in mm All dimensions in
Setting the Standard in Access Control
216
Electric Locking
NOR 200 M MONITORED
Shear Magnet
• Operating voltage 12~24Vdc • Holding force up to 1500lbs (680Kg) in shear
30
182
182
48
48
GS200-SH
GS200-GH
14
180
35
180
164
164
VOLTAGE SELECTION JUMPERS
MAGNET BOND SENSOR OUTPUT
N.C. output while door is unlocked; N.O. output while door is locked by the electromagnetic lock
Check jumper settings before connecting the lock to 24VDC input power. Damage to the lock may result from incorrect jumper settings.
N.C.
N.O. COM
Control Device N.C. Contactor or Access relay
27
33
Power Input SPDT relay
3A@30VDC
+ −
+ −
Power Supply
43
12Vdc 24Vdc
SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 500mA at 12Vdc, 250mA at 24Vdc (at temperature 20°C) . • Operating temperature: -30 ~ 55°C (-22 to 131°F) .
• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output-door closed) (GS-200M) (SPDT rated 3A at 30Vdc) .
• Humidity: 0 ~ 95% non-condensing. • Special Zinc finish for magnet and armature plate. • Weight: 2.0kg (approx) .
All dimensions in mm All dimensions in
Setting the Standard in Access Control
216
Electric Locking
NOR 220 Resettable Illuminated Call Point with Cover, Activation Sounder and Timer • Operating voltage 12~24Vdc • Green plastic • Resettable • Adjustable sounder • Adjustable LED • Triple pole
Alarm Mode Settings
MCP330PRO Contact 3 Status: Close Cover
LED
Buzzer
ON
ON
*
FLASH
BEEP
N.C. N.O. Com
OFF
*FACTORY SETTING
LED
Buzzer
Volume Adjusting
VOLUME DELAY
ON OFF FL ON SL BP
Volume
+
N.C1
SILENT
VCC
N.O1
LOW HIGH
MCP330PRO Contact 1 & 2 Status
GND
COM1
N.C3
N.C2
N.O3
N.O2
Time Delay
N.C. N.O. Com
COM3
COM2
0~60s
+
SILENT
Current Input (DC12-24V)
LOW HIGH
Switch Output Point (Max. load of 125VAC/3A)
Relay Output Point (Max. load of 125VAC/1A)
GREEN Display: Standby Status
MCP330PRO Contact 3 Status: Lift Cover
*Volume switch with maximum value, do not turn in 360.
N.C. N.O. Com
DC12V~24V +
LED Buzzer
ON OFF FL ON SL BP
VOLUME DELAY
N.C1
N.O1
VCC
MCP330PRO Contact 1 & 2 Status
Power Supply
COM1
GND
N.C2
N.C3
N.O2
N.O3
Monitoring System
N.C. N.O. Com
COM2
COM3
1. Voice and Green LED flash pre-alert when the cover is lifted, meanwhile the relay output is monitoring by system. 2. The delay time = Cover removing time + delay time (selecting by adjuster)
RED Display: Alarm Status
NOR 300L Adjustable L Bracket
• For Mini Magnets
All dimensions in mm
NOR 300BP Armature Mounting Plate
• Anodised Aluminium
All dimensions in mm
NOR 300CL Architectural L Bracket
• Anodised Aluminium • Bracket with Cover
All dimensions in mm
Setting the Standard
NOR 300ZL (B) Z & L Kit
• For Mini Magnets
All dimensions in mm
Setting the Standard
NOR 300ZLDC Architectural Z & L Bracket with Cover
• Anodised Aluminium
All dimensions in mm
NOR 300ZL DC -EXT P Z & L Extension
Extends 300ZL DC From 68 mm to 1 27 mm
Fully Adjustable
Aluminium
All dimensions in mm
Setting the Standard in Access Control
NOR 300ZL-G Z&L Kit • Z&L Kit For full Glass Door Applications • No Glue required
NOR 310MLS 12 VDC
Monitored Electric Release
• Operating voltage 12Vdc • Fail-Safe/Fail-Secure (Selectable) • Supplied with long and short plate • ANSI style electric release
FLEXIBLE SOLUTIONS
36.5
the NOR 310MlS electric strike can easily change between Fail-Safe and Fail-Secure modes. this unique design enables distributors to reduce inventory and still meet varying needs and requirements of end users.
33
31.8
33
2
1
Fail-Secure (Power to Open)
38
202
124
38
17
2
1
17
Fail-Safe (Power to Lock)
3
SPEC I F I CAT ION • Voltage tolerance: ±15%. • Current draw: 0.25A at 12Vdc, 0.15A at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 45°C (14 to 131°F) .
• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Sensor switch monitored output indicates lockset locked or unlocked status (SPDT rated 2A at 125Vdc) .
• Humidity: 0 ~ 95% non-condensing. • Horizontal or vertical installation. • Tested to 1,000,000 cycles • 2000lbs jaw strength pull testing.
All dimensions in mm
Setting the Standard in Access Control
Electric Locking
NOR 320M Armature Housing
• For Mini Magnets
All dimensions in mm
NOR33 0COVER Plastic cover
• Clear plastic cover • For break-glass unit MCP- 330-PRO
All dimensions in mm
Setting the Standard
NOR33 0KEY Plastic Key
• Clear plastic key • For break-glass unit MCP330PRO
All dimensions in mm
Setting the Standard
NOR330-PRO -PRO Resettable Illuminated Call Point with Cover, Activation Sounder and Timer
• Operating voltage 12~24Vdc • Green plastic • Resettable • Adjustable sounder • Adjustable LED • Triple pole • Alarmed cover sounder
OPTIONS
NOR 330Key
NOR 330 Cover
MCP330PRO Contact 3 Status: Close Cover MCP330PRO Contact 3 Status: Close Cover
Alarm Mode Settings
Alarm Mode Settings Buzzer LED
LED ON
Buzzer ON
85
N.C. N.O. Com
ON
ON
*
FLASH
BEEP
N.C. N.O. Com
*
FLASH
BEEP
OFF
OFF
*FACTORY SETTING
*FACTORY SETTING
LED
Buzzer
LED
Buzzer
Volume Adjusting Volume Adjusting
VOLUME DELAY
ON OFF FL ON SL BP
VOLUME DELAY
ON OFF FL ON SL BP
Volume
+
Volume
N.C1
+
N.C1
SILENT
SILENT
VCC
N.O1
VCC
N.O1
LOW HIGH LOW HIGH
MCP330PRO Contact 1 & 2 Status CP330PRO Contact 1 & 2 Status
85
GND
COM1
GND
COM1
N.C3
N.C2
N.C3
N.C2
N.O3
N.O2
N.O3
N.O2
Time Delay
Time Delay
N.C. N.O. Com
N.C. N.O. Com
COM3
COM2
COM3
COM2
0~60s
0~60s
+
SILENT
SILENT
Current Input (DC12-24V)
Current Input (DC12- 4V)
LOW HIGH LOW HIGH
Switch Output Point (Max. load of 125VAC/3A)
Switch Output Point (Max. load of 125VAC/3A)
Relay Output Point (Max. load of 125VAC/1A) Relay Output Point (Max. load of 125VAC/1A)
GREEN Display: Standby Status GREEN Display: Standby Status
MCP330PRO Contact 3 Status: Lift Cover MCP330PRO Contact 3 Status: Lift Cover
*Volume switch with maximum value, do not turn in 360. *Volume switch with maximum value, do not turn in 360.
25
N.C. N.O. Com
N.C. N.O. Com
DC12V~24V + DC12V~24V +
LED Buzzer
LED Buzzer
ON OFF FL ON SL BP
VOLUME DELAY
ON OFF FL ON SL BP
VOLUME DELAY
N.C1
N.C1
N.O1
VCC
Power Supply
N.O1
VCC
COM1
GND
MCP330PRO Contact 1 & 2 Status MCP330PRO Contact 1 & 2 Status
Power Supply
COM1
GND
N.C2
N.C3
N.O2
N.O3
N.C2
N.C3
Monitoring System Monitoring System
COM2
COM3
N.O2
N.O3
N.C. N.O. Com
COM2
COM3
N.C. N.O. Com
1. Voice and Green LED flash pre-alert when the cover is lifted, meanwhile the relay output is monitoring by system. 2. The delay time = Cover removing time + delay time (selecting by adjuster) 1. Voice and Green LED flash pre-alert when the cover is lifted, meanwhile the relay output is monitoring by system. 2. The delay time = Cover removing time + delay time (selecting by adjuster)
RED Display: Alarm Status
RED Display: Alarm Status
All dimensions in mm All dimensions in
Setting the Standard in Access Control
131
EXIT DEVICES
NOR 500 Micro Shearlock
OPTIONS
• Operating voltage 12~24Vdc • Holding force up to 2,600lbs (1,200Kg) in shear • Locking time delay: 0.5 to 25 seconds (Adjustable) • N.C/N.O/Com
NOR- BR500 • Surfac mounts for SL500
25
Reader
137
Exit Button
N.O.
COM.
N.C.
N.C.
COM.
182
Power Supply
30
Black
+ −
135
Red
DC 12 or 24V
30
24
NOR 500AL Adjustable L Bracket
• For Standard Magnets
All dimensions in mm
NOR 500BP Armature Mounting Plate for Standard Magnets
• Anodised Aluminium
All dimensions in mm
NOR 500 HOUSING Micro Shear-lock Bracket
• Surface housing
All dimensions in mm
Setting the Standard
NOR 500ZL (B) Z&L Kit
• For Standard Magnet
All dimensions in mm
Setting the Standard
NOR 500ZLDC Standard Z&L Bracket with Cover
• Anodised Aluminium
All dimensions in mm
NOR 5 00ZL DC -EXT P Z & L Extension
Extends 5 00ZL DC From 8 2 mm to 1 4 3 mm
Fully Adjustable
Aluminium
All dimensions in mm
Setting the Standard in Access Control
NOR 520S Armature Housing
• For Standard Brackets
All dimensions in mm
NOR 650S-12 12 VDC
Door Retaining Magnet
• Operating voltage 12Vdc • Stainless Steel • Fire tested: EN1155 • Up to 70lbs (32kg) holding force • Over-ride switch • Flush mount
STAINLESS STEEL
FIRE TESTED − EN1155 −
35
DOOR CLOSER
85
85
Power Input (12 or 24Vdc) from re ghting system
65
40
DOOR
43
65
WALL
SPEC I F I CAT ION • Voltage tolerance: ±15%. • Current draw: 150mA at 12Vdc, 70mA at 24Vdc (at temperature 20°C) .
• Operating temperature: -10 ~ 45°C (14 to 131°F) . • Humidity: 0 ~ 95% non-condensing.
• Weight: 380g (approx) .
All dimensions in mm
Setting the Standard in Access Control
Electric Locking
GD650S-24 24 VDC Door Retaining Magnet • Operating voltage 24 Vdc • Stainless Steel • Fire tested: EN1155 • Up to 70lbs (32kg) holding force • Over-ride switch • Flush mount
STAINLESS STEEL
FIRE TESTED − EN1155 −
35
DOOR CLOSER
85
85
Power Input (12 or 24Vdc) from re ghting system
65
40
DOOR
43
65
WALL
SPEC I F I CAT ION • Voltage tolerance: ±15%. • Current draw: 150mA at 12Vdc, 70mA at 24Vdc (at temperature 20°C) .
• Operating temperature: -10 ~ 45°C (14 to 131°F) . • Humidity: 0 ~ 95% non-condensing.
• Weight: 380g (approx) .
All dimensions in mm
Setting the Standard in Access Control
Electric Locking
NOR1200ZL Z&L Kit for Standard Magnet
• Anodised Aluminium •
All dimensions in mm
NOR ARCHRXE PRESS TO EXIT
Exit Button
• Gloss white plastic • Surface mount • COM / NO
H W D
85 33 25
NOR -DBB Double Back Box
• ABS plastic • Suitable for all Norbain exit buttons and break glass units • Horizontal or vertical • Surface mount • Internal cable ways
H W D 100 189 38
Exit Devices
42
All dimensions in mm
NOR DRB-IR Infra-Red Exit Button • Brushed Stainless Steel • Infra-Red • Adjustable timer • Flush mount • Surface mount option • Adjustable range • Change-over-contacts
INFRA-RED
H W D 85 85 30
DRB-IR • Flush mount
NOR- DRB -IR I R Button • Brushed Stainless Steel Plate • IR Button • Flush mount • COM-N/O COM-N/C • Supplied with security screws • 12VDC Operation
NOR- DRB -IR-1224 Surface IR Button
• Brushed Stainless Steel Plate • IR Button • Surface mount • COM-N/O COM-N/C • Supplied with security screws • Available in Sliver, Green or Black Housing • 12~24VDC Operation
Supplied as standard with Black Back Box
Order Codes DRB -IR-1224 ( BLACK ) DRB -IR-1224S (SILVER) DRB -IR-1224G ( Green )
50mm
40mm
NOR DRB -IR-1224 -WP Exit Button
• Infra Red Button • ABS Plastic • Legend: Door Release • Surface mount • Operation: 12~24VDC • Weather resistant: IP65 • COM-N/O COM-N/C
WEATHER RESISTANT − IP 65 −
85
85
40
Adjuster for Time Delay
Adjuster for detecting distance
Red cable:12-24VDC Black cable: 0VDC
Green:N.O Blue :COM Purple:N.C
PIN
Change-over Contact
Yel low: Green LED control led in EXT mode White:Red LED control led in EXT mode
Starting point
Adjuster for Time Delay
Adjuster for detecting distance
Starting point
-
-
+
+
0.5-20Seconds Toggle function: In the end of Clockwise position Starting Point: from “metal point”
5-20cm
All dimensions in mm
Setting the Standard in Access Control
EXIT DEVICES
NOR DRB -IR N Narrow IR Button • Brushed Stainless Steel Plate • IR Button • Flush mount • COM-N/O COM-N/C • 12~24VDC Operation
+ +
+ +
Internal Mode
External Mode
+ +
+ +
Adjustment for Time Delay 0.5~20 Seconds
Adjustment For Range 5 ~20cm
Specification
Voltage: 12~24VDC
Current: Max 45mA
Waterproof: IP65
Time Delay: 0.5~ 20sec
Toggle Mode: Yes
Range 5~20cm
Circuit Grade: 30VDC @ 1Amp
Contact: Com/NC/NO
Wiring:
Red - 12~24VDC
Black - 0VDC
Green - N/O
Blue - COM
Purple - N/C
Yellow - Green LED Ext Mode White - Red LED Ext Mode
NOR DRB -IR N Narrow IR Button • Brushed Stainless Steel Plate • IR Button • Flush mount • COM-N/O COM-N/C • 12~24VDC Operation
+ +
+ +
Internal Mode
External Mode
+ +
+ +
Adjustment for Time Delay 0.5~20 Seconds
Adjustment For Range 5 ~20cm
Specification
Voltage: 12~24VDC
Current: Max 45mA
Waterproof: IP65
Time Delay: 0.5~ 20sec
Toggle Mode: Yes
Range 5~20cm
Circuit Grade: 30VDC @ 1Amp
Contact: Com/NC/NO
Wiring:
Red - 12~24VDC
Black - 0VDC
Green - N/O
Blue - COM
Purple - N/C
Yellow - Green LED Ext Mode White - Red LED Ext Mode
NOR- DRB-SH Surface Housing
• Aluminium • Stainless Steel Effect
H W D 85 85 40
All dimensions in mm
Setting the Standard
NOR DRB-SH-N
Surface Housing
• Aluminium • Stainless Steel or Brushed Brass effect
H W D 85 38 40
All dimensions in mm
Setting the Standard in Access Control
EXIT DEVICES
NOR EX 2 - DR DOOR RELEASE Exit Button
• Gloss white plastic • Surface mount • COM-N/O/NC
H W D 85 85 27
All dimensions in mm
Setting the Standard in Access Control
EXIT DEVICES
NOR MDL-01 Mechanical Door Lock
• Zinc Alloy • Remove lock from door to change code • Code in / Code out: No • Single code storage only • For door thickness 35-65mm (13/8"-21/2") • For left or right handed doors • 2 part 8mm (5/ 16") spring loaded spindle • Internal or external use • Type to front and back plates only
25
32
42
1 2 3 4 5 X Y
6 7 8 9 0 Z C
142
60
40
16
All dimensions in mm
Setting the Standard in Access Control
ACCESS CONTROL
NOR P OST -M-G Steel Posts
• Car or pedestrian height • Pre-drilled cable entry • Adaptable mounting plate • Optional special finishes
3
120
Ø25
220
220
1000
670
Ø25
25
Ø11.5 x 4
3
300
50
All dimensions in mm All dimensions in
Setting the Standard in Access Control
78
ADDITIONAL EQUIPMENT
NORPOST-SS-BG-CUT Stainless Steel Posts
• With BGU cut-out • Car or pedestrian height • Round • Stainless Steel construction • Unique interchangable mounting
CAMERA/ CALL BUTTON CONTROL PANEL
PROXIMITY READER CONTROL PANEL
STAINLESS STEEL
KEYPAD CONTROL PANEL
FOR CUSTOMER FITTED CONTROL PANELS
Ø127
45 o
BGU CUT-OUT FOR CUSTOMER FITTED EXIT DEVICES
1000
250
5
250
All dimensions in mm All dimensions in
Setting the Standard in Access Control
80
ADDITIONAL EQUIPMENT
S P-2 Call Point Protector • Polycarbonate construction • Surface mount • Can retrofit over existing device • Red and green covers supplied • Built-in sounder
SPEC I F I CAT ION • Protective cover helps prevent malicious or accidental false fire alarms • Three year guarantee against breakage
• Operating temperature: -40 ~ 49°C (-40 to 120°F) . • Break seal option for added security.
• Available with or without a 96dB integral sounder powered by a 3V lithium battery.
Made with FlippingBook - Online catalogs