NOR01(B)-FIRE

ACCESS CONTROL ACCESSORIES

FIRE RATED PRODUCTS

NOR 01(B)-FIRE Unmonitored Mini Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe

UK FIRE TESTED

DOORS BS EN1634:1 FD30 & FD60

BS EN1634:1

Power Supply

+

250

+

11

6

JP1

42

180

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

26

38

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .

NOR0 1 (B) Unmonitored Mini Magnet

• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe

Power Supply

+

250

+

11

6

JP1

42

180

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

26

38

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .

All dimensions in mm

NOR01 EXTP Extended Top Plate for Mini Magnet

• Anodised Aluminium

NOR 1A-12VL Power Supply • 220Vac power input • 12Vdc 1Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 305 304 85

NOR 1A-12VS Smallbox Power Supply • 220Vac power input • 12Vdc 1Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 225 195 80

NOR 1A- 24 VL Power Supply • 220Vac power input • 24 Vdc 1Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 305 304 85

FIRE RATED PRODUCTS

NOR02 (B)-FIRE Monitored Mini Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe • Status LED ● Red ● Green

UK FIRE TESTED

DOORS BS EN1634:1 FD30 & FD60

BS EN1634:1

Power Supply

Contact

+

250

+

N.O.

N.C.

C

11

6

JP1

42

180

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

26

38

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output

door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .

NOR02(B) Monitored Mini Magnet

• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe • Status LED ● Red ● Green

Power Supply

Contact

+

250

+

N.O.

N.C.

C

11

6

JP1

42

180

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

26

38

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output

door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .

All dimensions in mm

NOR02 DS (B) Monitored Mini Magnet With Door Status

• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Door Status Monitoring • Lock Monitoring

• Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe • Status LED ● Red ● Green

Power Supply

Contact

Contact

+

250

+

N.O.

N.O.

C

N.C.

C

11

6

JP1

42

190

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

26

38

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output

door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .

All dimensions in mm

NOR 2 A- 12 VL Power Supply • 220Vac power input • 12 Vdc 2 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 305 304 85

NOR 2 A-12VS Smallbox Power Supply • 220Vac power input • 12Vdc 2 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 225 195 80

NOR 003N Plastic Cover

• Clear plastic cover • For break-glass unit

All dimensions in mm

Setting the Standard

NOR 3 A- 12 VL Power Supply • 220Vac power input • 12 Vdc 3 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 305 304 85

NOR 3 A-12VS Smallbox Power Supply • 220Vac power input • 12Vdc 3 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 225 195 80

NOR 3 A- 24 VL Power Supply • 220Vac power input • 24 Vdc 3 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 305 304 85

NOR 004F -PTE Exit Button

• Brushed Stainless Steel •

Green dome button

• Flush mount • FREE : Add your company logo • COM-N/O COM-N/C

OPTIONS

NOR- DRB-SH

NOR 004F-PTE PRESS TO EXIT

M22 x P1.5

2

85

35

29.9

5

85

23

Ø22

0.6 Thickness

45

Operating Travel 2.7

FREE POSITION

OPERATING POSITION

SPEC I F I CAT ION • Max. Rating: 5A/125/250 Vac. • Contact resistance: 50mΩ Max. (Initial) . • Operating travel: 2.7mm.

• Operating life (Mechanical) : Over 100,000 times. • Cables included.

All dimensions in mm

EXIT DEVICES

NOR 004S-PTE PRESS TO EXIT Exit Button

• Brushed Stainless Steel •

Green dome button

• Surface mount • FREE : Add your company logo • COM-N/O COM-N/C

M22 x P1.5

40

85

2

35

29.9

5

23

0.6 Thickness

85

Ø22

45

Operating Travel 2.7

FREE POSITION

OPERATING POSITION

SPEC I F I CAT ION • Max. Rating: 5A/125/250 Vac. • Contact resistance: 50mΩ Max. (Initial) • Operating travel: 2.7mm.

• Operating life (Mechanical) : Over 100,000 times. • Cables included.

NOR04(B) Unmonitored Double Mini Magnet

• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 2 x 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe

Power Supply

+

11

500

+

180

38

JP1

6

42

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

26

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 3.7kg (approx) .

All dimensions in mm

NOR0 5 (B) Monitored Double Mini Magnet

• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 2 x 600lbs (272Kg) • Electro-less Nickel Plated Armature • Status LED ● Red ● Green

Power Supply

Contact

+

11

500

+

N.O.

N.C.

C

180

38

JP1

6

42

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

26

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) .

• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Humidity: 0 ~ 95% non-condensing. • Weight: 3.7kg (approx) .

• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output-door closed) (SPDT rated 0.25A at 12Vdc) .

All dimensions in mm

NOR0 5 DS (B) Monitored Mini Magnet With Door Status

• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Door Status Monitoring • Lock Monitoring

• Holding force up to 600lbs (272Kg) • Electro-less Nickel Plated Armature • Fail-Safe • Status LED ● Red ● Green

Power Supply

Contact

Contact

+

11

500

+

N.O.

N.O.

C

N.C.

C

190

38

JP1

6

42

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

26

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 480mA at 12Vdc, 240mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output

door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 2.0kg (approx) .

All dimensions in mm

NOR 5 A- 12 VL Power Supply • 220Vac power input • 12 Vdc 5 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 305 304 85

NOR 5 A- 24 VL Power Supply • 220Vac power input • 24 Vdc 5 Amp output • Metal hinged box • Deep discharge protection • LED Indicators • Key lockable • Battery charging circuit

SWITCH

H W D 305 304 85

NOR 008F-PTE PRESS TO EXIT

Exit Button

• Stainless Steel • Green finish • Raised green dome button • Flush mount • COM-N/O COM-N/C

M22 x P1.5

22 17.5

85

5

85

23

0.6 Thickness

Ø22

28.2

Operating Travel 2.7

FREE POSITION

OPERATING POSITION

SPEC I F I CAT ION • Max. Rating: 5A/125/250 Vac. • Contact resistance: 50mΩ Max. (Initial) . • Operating travel: 2.7mm.

• Operating life (Mechanical) : Over 100,000 times. • Cables included.

All dimensions in mm

Setting the Standard in Access Control

EXIT DEVICES

FIRE RATED PRODUCTS

NOR10(B)-FIRE Unmonitored Standard Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 1200lbs (544Kg) • Electro-less nickel plated armature

UK FIRE TESTED

DOORS BS EN1634:1 FD30 & FD60

BS EN1634:1

Power Supply

+

268

+

9

17

JP1

67

185

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

40

61

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 4.71kg (approx) .

NOR 10 (B) Unmonitored Standard Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 1200lbs (544Kg) • Electro-less nickel plated armature

Power Supply

+

268

+

9

17

JP1

67

185

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

40

61

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 4.71kg (approx) .

All dimensions in mm

NOR10 EXTP Extended Top Plate for Standard Magnet

• Anodised Aluminium

NOR12/24(B) External Magnet

• Operating voltage 12~24Vdc (Selectable) • Stainless Steel housing • Holding force up to 1200lbs (545Kg) • Weather resistant: IP67 • Sealed electronics

WEATHER RESISTANT − IP 67 −

STAINLESS STEEL

222

17

62

185

42

61

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) .

• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Humidity: 0 ~ 95% non-condensing. • Weight: 3.7kg (approx) .

• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output-door closed) (SPDT rated 0.25A at 12Vdc) .

188

NOR 014S-PTE Exit Button

• ABS Plastic • Legend: Press to Exit • • Surface mount • Weather resistant: IP65 • COM-N/O COM-N/C

Green dome button

WEATHER RESISTANT − IP 65 −

M22 x P1.5

2

35

29.9

85

5

23

0.6 Thickness

85

45

Operating Travel 2.7

40

FREE POSITION

OPERATING POSITION

SPEC I F I CAT ION • Max. Rating: 5A/125/250 Vac. • Contact resistance: 50mΩ Max. (Initial) • Operating travel: 2.7mm.

• Operating life (Mechanical) : Over 100,000 times. • Cables included.

NOR15 Breakglass Call Point

• Green plastic • Break glass • Surface mount

NOR 15 • Single pole

OPTIONS

NOR 15 N- Key (5)

NOR003N

Power Supply

+

+

+

85

Electromagnetic Locks (Locked)

51

Alarm

Y

GENC

EMER

EASE

RREL

85

DOO

E

SHER

PRES

Power Supply

+

+

+

Electromagnetic Locks (Unlocked)

Alarm

Spec i f i cat ion • COM / NO / NC Change-over-contacts x 2

• Contact resistance 150m • Contact resistance 3A @125V ac

FIRE RATED PRODUCTS

NOR 20 (B)-FIRE Monitored Standard Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 1200lbs (544Kg) • Electro-less nickel plated armature • Status LED ● Red ● Green

UK FIRE TESTED

DOORS BS EN1634:1 FD30 & FD60

BS EN1634:1

Power Supply

Contact

+

268

+

N.O.

N.C.

C

9

17

JP1

67

185

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

40

61

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output

door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 4.71kg (approx) .

NOR 20 (B) Monitored Standard Magnet • Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 1200lbs (544Kg) • Electro-less nickel plated armature • Status LED ● Red ● Green

Power Supply

Contact

+

268

+

N.O.

N.C.

C

9

17

JP1

67

185

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

40

61

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output

door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight: 4.71kg (approx) .

All dimensions in mm

NOR21KEY-N(5) Key

• Black plastic key • For break-glass unit • Pack of 5

All dimensions in mm

Setting the Standard

NOR 21-N 2 POLE Breakglass Call Point

• Green plastic • Break glass • Surface mount

OPTIONS

NOR0 03-N

NOR 21N -Key(5)

88

Power Supply

60

+

+

+

Electromagnetic Locks (Locked)

Alarm

Y

GENC

EMER

EASE

RREL

88

DOO

E

SHER

PRES

Power Supply

+

Reset key

+

+

Switch 2

Switch 1

Electromagnetic Locks (Unlocked)

Alarm

SPEC I F I CAT ION • COM / NO / NC Change-over-contacts x 2

• Contact resistance 150m • Contact resistance 3A @125V ac

NOR 22-3- KEY Plastic Key • Clear plastic key • For External B reak- G lass U nit NOR-22-3WP

All dimensions in mm

Setting the Standard

NOR 22-3WP Waterproof Breakglass Call Point

• Green plastic • Triple pole • Resettable • Surface mount • Externally rated weatherproof • COM / NO / NC Change-over-contacts x 3

WEATHER RESISTANT − IP 67 −

H W D 135 125 62

All dimensions in mm All dimensions in

Setting the Standard in Access Control

134

EXIT DEVICES

NOR2 2 KEY-N(5) Key

• Black plastic key • For break-glass unit • Pack of 5

All dimensions in mm

Setting the Standard

NOR22N-EDR Resettable Call Point

• Green plastic • Resettable • Surface mount

OPTIONS

CP22-N Key

MXO03-N

88

Power Supply

60

+

+

+

Electromagnetic Locks (Locked)

Alarm

Y

GENC

EMER

EASE

RREL

88

DOO

E

SHER

PRES

Power Supply

+

Reset key

+

+

Switch 2

Switch 1

Electromagnetic Locks (Unlocked)

Alarm

SPEC I F I CAT ION • COM / NO / NC Change-over-contacts x 2

• Contact resistance 150m • Contact resistance 3A @125V ac

NOR 40DS (B) Double Standard Magnet

• Operating voltage 12~24Vdc (Selectable) • Holding force up to 2 X 1200lbs (544Kg) • Aluminium housing • Electroless nickel plated armature • Door status: An independent contact that works separately from the magnet to show door status not lock status • Status LED ● Red ● Green

MONITORED WITH DOOR STATUS

Power Supply

Contact

+

532

+

N.O.

N.C.

C

185

17

61

9

JP1

67

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

40

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output

door closed) (SPDT rated 0.25A at 12Vdc) . • Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight:9.3kg (approx) .

All dimensions in mm

Setting the Standard in Access Control

183

Electric Locking

EXIT DEVICES

DRB0 44S Series Budget Green Dome Button

• Brushed Stainless Steel Plate • Budget green dome button • Surface mount • COM-N/O COM-N/C • Supplied with security screws • Available in Green or Black Housing

Order Codes DRB044S-PTE ( GREEN)

50mm

40mm

All dimensions in mm

Safety straps available from Norbain for the Mini and Standard Magnets and the Mini and Standard Armatures, bringing an extra level of safety to our magnetic and Armature products. Safety Straps for Magnetic Locks Bringing extra safety to electric locking

MAG-55 Safety Strap.

Safety Straps for Standard or Mini Armatures

Safety Straps for Standard or Mini Armatures

All dimensions in mm

Setting the Standard in Access Control

AUDIO AND VIDEO ENTRY

NOR 60 (B) Unmonitored Double Standard Magnet

• Operating voltage 12~24Vdc (Selectable) • Aluminium housing • Holding force up to 2 x 1200lbs (544Kg) • Electro-less nickel plated armature

Power Supply

+

532

+

185

17

61

9

JP1

67

CAUTION Before power on the unit, set input Voltage Selector JP1 according to the supply voltage.

40

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 420mA at 12Vdc, 210mA at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 55°C (14 to 131°F) . • Lock’s surface temperature: Current temperature ±20% (when power is on) .

• Humidity: 0 ~ 95% non-condensing. • Aluminium housing, nickel plated armature. • Weight:9.3kg (approx) .

All dimensions in mm

Setting the Standard

NOR 165 Soleniod Bolt

• Operating voltage 12Vdc (24Vdc available to order) • Die-Cast Metal • Fail-Safe • Adjustable Timer • Monitored

JP3: Control ML-350 to be locked by door status.

It is applied to fail-safe mode only.

JP3: Power to lock without any devices.

SPEC I F I CAT ION • Voltage 12VDC . • Current draw: 570 mA at 12Vdc • Monitoring: N/C Contact

• Adjustable Timer 0~3 seconds . • Operational Door Gap 6mm Max • Bolt : 14mm throw, 12.7mm Diameter

All dimensions in mm

Setting the Standard in Access Control

Electric Locking

NOR 180 Electric Dropbolt

• Operating voltage 12~24Vdc • Stainless Steel • Fail-Safe (Power to Lock) • Vandal resistant • Built-in logical circuitry • Auto-relocking timer delay: 0, 3, 6 or 9 seconds

VANDAL RESISTANT

STAINLESS STEEL

16.5

Ø5.3xØ10.5 (2 Places)

30.8

Ø9.9

24

57.5

AUTO RELOCKING TIMER SETTINGS

45

20

Use jumpers to adjust the time between 0 to 9 seconds for door locking time delay. This is the time, which takes the dropbolt to automatically lock after the door is closed.

100 75

R8

210

149

185

R12.5

ON 1 2

ON 1 2

140

0 Seconds

3 Seconds

ON 1 2

1 2

ON

6 Seconds

9 Seconds

3

30.2

12.5

25

41

10

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: Pull in 0.9A, Holding 0.3A at 12Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 45°C (14 to 131°F) .

• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Magnetic bolt status output indicates bolt locked or unlocked status (SPDT rated 3A at 30Vdc) .

• Humidity: 0 ~ 95% non-condensing. • Horizontal or vertical installation. • Face plate material: Stainless Steel.

• Tested to 500,000 cycles. • Weight: 0.6kg (approx) .

All dimensions in mm

Setting the Standard in Access Control

Electric Locking

NOR 200 UNMONITORED

Shear Magnet

• Operating voltage 12~24Vdc • Holding force up to 1500lbs (680Kg) in shear

30

182

182

48

48

GS200-SH

GS200-GH

14

180

35

180

164

164

VOLTAGE SELECTION JUMPERS

MAGNET BOND SENSOR OUTPUT

N.C. output while door is unlocked; N.O. output while door is locked by the electromagnetic lock

Check jumper settings before connecting the lock to 24VDC input power. Damage to the lock may result from incorrect jumper settings.

N.C.

N.O. COM

Control Device N.C. Contactor or Access relay

27

33

Power Input SPDT relay

3A@30VDC

+ −

+ −

Power Supply

43

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 500mA at 12Vdc, 250mA at 24Vdc (at temperature 20°C) . • Operating temperature: -30 ~ 55°C (-22 to 131°F) .

• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output-door closed) (GS-200M) (SPDT rated 3A at 30Vdc) .

• Humidity: 0 ~ 95% non-condensing. • Special Zinc finish for magnet and armature plate. • Weight: 2.0kg (approx) .

All dimensions in mm All dimensions in

Setting the Standard in Access Control

216

Electric Locking

NOR 200 M MONITORED

Shear Magnet

• Operating voltage 12~24Vdc • Holding force up to 1500lbs (680Kg) in shear

30

182

182

48

48

GS200-SH

GS200-GH

14

180

35

180

164

164

VOLTAGE SELECTION JUMPERS

MAGNET BOND SENSOR OUTPUT

N.C. output while door is unlocked; N.O. output while door is locked by the electromagnetic lock

Check jumper settings before connecting the lock to 24VDC input power. Damage to the lock may result from incorrect jumper settings.

N.C.

N.O. COM

Control Device N.C. Contactor or Access relay

27

33

Power Input SPDT relay

3A@30VDC

+ −

+ −

Power Supply

43

12Vdc 24Vdc

SPEC I F I CAT ION • Voltage tolerance: ±10%. • Current draw: 500mA at 12Vdc, 250mA at 24Vdc (at temperature 20°C) . • Operating temperature: -30 ~ 55°C (-22 to 131°F) .

• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Magnetic bond sensor monitor output remotely monitors the door lock or unlock status. (N.C. Output-Door opened; N.O. Output-door closed) (GS-200M) (SPDT rated 3A at 30Vdc) .

• Humidity: 0 ~ 95% non-condensing. • Special Zinc finish for magnet and armature plate. • Weight: 2.0kg (approx) .

All dimensions in mm All dimensions in

Setting the Standard in Access Control

216

Electric Locking

NOR 220 Resettable Illuminated Call Point with Cover, Activation Sounder and Timer • Operating voltage 12~24Vdc • Green plastic • Resettable • Adjustable sounder • Adjustable LED • Triple pole

Alarm Mode Settings

MCP330PRO Contact 3 Status: Close Cover

LED

Buzzer

ON

ON

*

FLASH

BEEP

N.C. N.O. Com

OFF

*FACTORY SETTING

LED

Buzzer

Volume Adjusting

VOLUME DELAY

ON OFF FL ON SL BP

Volume

+

N.C1

SILENT

VCC

N.O1

LOW HIGH

MCP330PRO Contact 1 & 2 Status

GND

COM1

N.C3

N.C2

N.O3

N.O2

Time Delay

N.C. N.O. Com

COM3

COM2

0~60s

+

SILENT

Current Input (DC12-24V)

LOW HIGH

Switch Output Point (Max. load of 125VAC/3A)

Relay Output Point (Max. load of 125VAC/1A)

GREEN Display: Standby Status

MCP330PRO Contact 3 Status: Lift Cover

*Volume switch with maximum value, do not turn in 360.

N.C. N.O. Com

DC12V~24V +

LED Buzzer

ON OFF FL ON SL BP

VOLUME DELAY

N.C1

N.O1

VCC

MCP330PRO Contact 1 & 2 Status

Power Supply

COM1

GND

N.C2

N.C3

N.O2

N.O3

Monitoring System

N.C. N.O. Com

COM2

COM3

1. Voice and Green LED flash pre-alert when the cover is lifted, meanwhile the relay output is monitoring by system. 2. The delay time = Cover removing time + delay time (selecting by adjuster)

RED Display: Alarm Status

NOR 300L Adjustable L Bracket

• For Mini Magnets

All dimensions in mm

NOR 300BP Armature Mounting Plate

• Anodised Aluminium

All dimensions in mm

NOR 300CL Architectural L Bracket

• Anodised Aluminium • Bracket with Cover

All dimensions in mm

Setting the Standard

NOR 300ZL (B) Z & L Kit

• For Mini Magnets

All dimensions in mm

Setting the Standard

NOR 300ZLDC Architectural Z & L Bracket with Cover

• Anodised Aluminium

All dimensions in mm

NOR 300ZL DC -EXT P Z & L Extension

Extends 300ZL DC From 68 mm to 1 27 mm

Fully Adjustable

Aluminium

All dimensions in mm

Setting the Standard in Access Control

NOR 300ZL-G Z&L Kit • Z&L Kit For full Glass Door Applications • No Glue required

NOR 310MLS 12 VDC

Monitored Electric Release

• Operating voltage 12Vdc • Fail-Safe/Fail-Secure (Selectable) • Supplied with long and short plate • ANSI style electric release

FLEXIBLE SOLUTIONS

36.5

the NOR 310MlS electric strike can easily change between Fail-Safe and Fail-Secure modes. this unique design enables distributors to reduce inventory and still meet varying needs and requirements of end users.

33

31.8

33

2

1

Fail-Secure (Power to Open)

38

202

124

38

17

2

1

17

Fail-Safe (Power to Lock)

3

SPEC I F I CAT ION • Voltage tolerance: ±15%. • Current draw: 0.25A at 12Vdc, 0.15A at 24Vdc (at temperature 20°C) . • Operating temperature: -10 ~ 45°C (14 to 131°F) .

• Lock’s surface temperature: Current temperature ±20% (when power is on) . • Sensor switch monitored output indicates lockset locked or unlocked status (SPDT rated 2A at 125Vdc) .

• Humidity: 0 ~ 95% non-condensing. • Horizontal or vertical installation. • Tested to 1,000,000 cycles • 2000lbs jaw strength pull testing.

All dimensions in mm

Setting the Standard in Access Control

Electric Locking

NOR 320M Armature Housing

• For Mini Magnets

All dimensions in mm

NOR33 0COVER Plastic cover

• Clear plastic cover • For break-glass unit MCP- 330-PRO

All dimensions in mm

Setting the Standard

NOR33 0KEY Plastic Key

• Clear plastic key • For break-glass unit MCP330PRO

All dimensions in mm

Setting the Standard

NOR330-PRO -PRO Resettable Illuminated Call Point with Cover, Activation Sounder and Timer

• Operating voltage 12~24Vdc • Green plastic • Resettable • Adjustable sounder • Adjustable LED • Triple pole • Alarmed cover sounder

OPTIONS

NOR 330Key

NOR 330 Cover

MCP330PRO Contact 3 Status: Close Cover MCP330PRO Contact 3 Status: Close Cover

Alarm Mode Settings

Alarm Mode Settings Buzzer LED

LED ON

Buzzer ON

85

N.C. N.O. Com

ON

ON

*

FLASH

BEEP

N.C. N.O. Com

*

FLASH

BEEP

OFF

OFF

*FACTORY SETTING

*FACTORY SETTING

LED

Buzzer

LED

Buzzer

Volume Adjusting Volume Adjusting

VOLUME DELAY

ON OFF FL ON SL BP

VOLUME DELAY

ON OFF FL ON SL BP

Volume

+

Volume

N.C1

+

N.C1

SILENT

SILENT

VCC

N.O1

VCC

N.O1

LOW HIGH LOW HIGH

MCP330PRO Contact 1 & 2 Status CP330PRO Contact 1 & 2 Status

85

GND

COM1

GND

COM1

N.C3

N.C2

N.C3

N.C2

N.O3

N.O2

N.O3

N.O2

Time Delay

Time Delay

N.C. N.O. Com

N.C. N.O. Com

COM3

COM2

COM3

COM2

0~60s

0~60s

+

SILENT

SILENT

Current Input (DC12-24V)

Current Input (DC12- 4V)

LOW HIGH LOW HIGH

Switch Output Point (Max. load of 125VAC/3A)

Switch Output Point (Max. load of 125VAC/3A)

Relay Output Point (Max. load of 125VAC/1A) Relay Output Point (Max. load of 125VAC/1A)

GREEN Display: Standby Status GREEN Display: Standby Status

MCP330PRO Contact 3 Status: Lift Cover MCP330PRO Contact 3 Status: Lift Cover

*Volume switch with maximum value, do not turn in 360. *Volume switch with maximum value, do not turn in 360.

25

N.C. N.O. Com

N.C. N.O. Com

DC12V~24V + DC12V~24V +

LED Buzzer

LED Buzzer

ON OFF FL ON SL BP

VOLUME DELAY

ON OFF FL ON SL BP

VOLUME DELAY

N.C1

N.C1

N.O1

VCC

Power Supply

N.O1

VCC

COM1

GND

MCP330PRO Contact 1 & 2 Status MCP330PRO Contact 1 & 2 Status

Power Supply

COM1

GND

N.C2

N.C3

N.O2

N.O3

N.C2

N.C3

Monitoring System Monitoring System

COM2

COM3

N.O2

N.O3

N.C. N.O. Com

COM2

COM3

N.C. N.O. Com

1. Voice and Green LED flash pre-alert when the cover is lifted, meanwhile the relay output is monitoring by system. 2. The delay time = Cover removing time + delay time (selecting by adjuster) 1. Voice and Green LED flash pre-alert when the cover is lifted, meanwhile the relay output is monitoring by system. 2. The delay time = Cover removing time + delay time (selecting by adjuster)

RED Display: Alarm Status

RED Display: Alarm Status

All dimensions in mm All dimensions in

Setting the Standard in Access Control

131

EXIT DEVICES

NOR 500 Micro Shearlock

OPTIONS

• Operating voltage 12~24Vdc • Holding force up to 2,600lbs (1,200Kg) in shear • Locking time delay: 0.5 to 25 seconds (Adjustable) • N.C/N.O/Com

NOR- BR500 • Surfac mounts for SL500

25

Reader

137

Exit Button

N.O.

COM.

N.C.

N.C.

COM.

182

Power Supply

30

Black

+ −

135

Red

DC 12 or 24V

30

24

NOR 500AL Adjustable L Bracket

• For Standard Magnets

All dimensions in mm

NOR 500BP Armature Mounting Plate for Standard Magnets

• Anodised Aluminium

All dimensions in mm

NOR 500 HOUSING Micro Shear-lock Bracket

• Surface housing

All dimensions in mm

Setting the Standard

NOR 500ZL (B) Z&L Kit

• For Standard Magnet

All dimensions in mm

Setting the Standard

NOR 500ZLDC Standard Z&L Bracket with Cover

• Anodised Aluminium

All dimensions in mm

NOR 5 00ZL DC -EXT P Z & L Extension

Extends 5 00ZL DC From 8 2 mm to 1 4 3 mm

Fully Adjustable

Aluminium

All dimensions in mm

Setting the Standard in Access Control

NOR 520S Armature Housing

• For Standard Brackets

All dimensions in mm

NOR 650S-12 12 VDC

Door Retaining Magnet

• Operating voltage 12Vdc • Stainless Steel • Fire tested: EN1155 • Up to 70lbs (32kg) holding force • Over-ride switch • Flush mount

STAINLESS STEEL

FIRE TESTED − EN1155 −

35

DOOR CLOSER

85

85

Power Input (12 or 24Vdc) from re ghting system

65

40

DOOR

43

65

WALL

SPEC I F I CAT ION • Voltage tolerance: ±15%. • Current draw: 150mA at 12Vdc, 70mA at 24Vdc (at temperature 20°C) .

• Operating temperature: -10 ~ 45°C (14 to 131°F) . • Humidity: 0 ~ 95% non-condensing.

• Weight: 380g (approx) .

All dimensions in mm

Setting the Standard in Access Control

Electric Locking

GD650S-24 24 VDC Door Retaining Magnet • Operating voltage 24 Vdc • Stainless Steel • Fire tested: EN1155 • Up to 70lbs (32kg) holding force • Over-ride switch • Flush mount

STAINLESS STEEL

FIRE TESTED − EN1155 −

35

DOOR CLOSER

85

85

Power Input (12 or 24Vdc) from re ghting system

65

40

DOOR

43

65

WALL

SPEC I F I CAT ION • Voltage tolerance: ±15%. • Current draw: 150mA at 12Vdc, 70mA at 24Vdc (at temperature 20°C) .

• Operating temperature: -10 ~ 45°C (14 to 131°F) . • Humidity: 0 ~ 95% non-condensing.

• Weight: 380g (approx) .

All dimensions in mm

Setting the Standard in Access Control

Electric Locking

NOR1200ZL Z&L Kit for Standard Magnet

• Anodised Aluminium •

All dimensions in mm

NOR ARCHRXE PRESS TO EXIT

Exit Button

• Gloss white plastic • Surface mount • COM / NO

H W D

85 33 25

NOR -DBB Double Back Box

• ABS plastic • Suitable for all Norbain exit buttons and break glass units • Horizontal or vertical • Surface mount • Internal cable ways

H W D 100 189 38

Exit Devices

42

All dimensions in mm

NOR DRB-IR Infra-Red Exit Button • Brushed Stainless Steel • Infra-Red • Adjustable timer • Flush mount • Surface mount option • Adjustable range • Change-over-contacts

INFRA-RED

H W D 85 85 30

DRB-IR • Flush mount

NOR- DRB -IR I R Button • Brushed Stainless Steel Plate • IR Button • Flush mount • COM-N/O COM-N/C • Supplied with security screws • 12VDC Operation

NOR- DRB -IR-1224 Surface IR Button

• Brushed Stainless Steel Plate • IR Button • Surface mount • COM-N/O COM-N/C • Supplied with security screws • Available in Sliver, Green or Black Housing • 12~24VDC Operation

Supplied as standard with Black Back Box

Order Codes DRB -IR-1224 ( BLACK ) DRB -IR-1224S (SILVER) DRB -IR-1224G ( Green )

50mm

40mm

NOR DRB -IR-1224 -WP Exit Button

• Infra Red Button • ABS Plastic • Legend: Door Release • Surface mount • Operation: 12~24VDC • Weather resistant: IP65 • COM-N/O COM-N/C

WEATHER RESISTANT − IP 65 −

85

85

40

Adjuster for Time Delay

Adjuster for detecting distance

Red cable:12-24VDC Black cable: 0VDC

Green:N.O Blue :COM Purple:N.C

PIN

Change-over Contact

Yel low: Green LED control led in EXT mode White:Red LED control led in EXT mode

Starting point

Adjuster for Time Delay

Adjuster for detecting distance

Starting point

-

-

+

+

0.5-20Seconds Toggle function: In the end of Clockwise position Starting Point: from “metal point”

5-20cm

All dimensions in mm

Setting the Standard in Access Control

EXIT DEVICES

NOR DRB -IR N Narrow IR Button • Brushed Stainless Steel Plate • IR Button • Flush mount • COM-N/O COM-N/C • 12~24VDC Operation

+ +

+ +

Internal Mode

External Mode

+ +

+ +

Adjustment for Time Delay 0.5~20 Seconds

Adjustment For Range 5 ~20cm

Specification

Voltage: 12~24VDC

Current: Max 45mA

Waterproof: IP65

Time Delay: 0.5~ 20sec

Toggle Mode: Yes

Range 5~20cm

Circuit Grade: 30VDC @ 1Amp

Contact: Com/NC/NO

Wiring:

Red - 12~24VDC

Black - 0VDC

Green - N/O

Blue - COM

Purple - N/C

Yellow - Green LED Ext Mode White - Red LED Ext Mode

NOR DRB -IR N Narrow IR Button • Brushed Stainless Steel Plate • IR Button • Flush mount • COM-N/O COM-N/C • 12~24VDC Operation

+ +

+ +

Internal Mode

External Mode

+ +

+ +

Adjustment for Time Delay 0.5~20 Seconds

Adjustment For Range 5 ~20cm

Specification

Voltage: 12~24VDC

Current: Max 45mA

Waterproof: IP65

Time Delay: 0.5~ 20sec

Toggle Mode: Yes

Range 5~20cm

Circuit Grade: 30VDC @ 1Amp

Contact: Com/NC/NO

Wiring:

Red - 12~24VDC

Black - 0VDC

Green - N/O

Blue - COM

Purple - N/C

Yellow - Green LED Ext Mode White - Red LED Ext Mode

NOR- DRB-SH Surface Housing

• Aluminium • Stainless Steel Effect

H W D 85 85 40

All dimensions in mm

Setting the Standard

NOR DRB-SH-N

Surface Housing

• Aluminium • Stainless Steel or Brushed Brass effect

H W D 85 38 40

All dimensions in mm

Setting the Standard in Access Control

EXIT DEVICES

NOR EX 2 - DR DOOR RELEASE Exit Button

• Gloss white plastic • Surface mount • COM-N/O/NC

H W D 85 85 27

All dimensions in mm

Setting the Standard in Access Control

EXIT DEVICES

NOR MDL-01 Mechanical Door Lock

• Zinc Alloy • Remove lock from door to change code • Code in / Code out: No • Single code storage only • For door thickness 35-65mm (13/8"-21/2") • For left or right handed doors • 2 part 8mm (5/ 16") spring loaded spindle • Internal or external use • Type to front and back plates only

25

32

42

1 2 3 4 5 X Y

6 7 8 9 0 Z C

142

60

40

16

All dimensions in mm

Setting the Standard in Access Control

ACCESS CONTROL

NOR P OST -M-G Steel Posts

• Car or pedestrian height • Pre-drilled cable entry • Adaptable mounting plate • Optional special finishes

3

120

Ø25

220

220

1000

670

Ø25

25

Ø11.5 x 4

3

300

50

All dimensions in mm All dimensions in

Setting the Standard in Access Control

78

ADDITIONAL EQUIPMENT

NORPOST-SS-BG-CUT Stainless Steel Posts

• With BGU cut-out • Car or pedestrian height • Round • Stainless Steel construction • Unique interchangable mounting

CAMERA/ CALL BUTTON CONTROL PANEL

PROXIMITY READER CONTROL PANEL

STAINLESS STEEL

KEYPAD CONTROL PANEL

FOR CUSTOMER FITTED CONTROL PANELS

Ø127

45 o

BGU CUT-OUT FOR CUSTOMER FITTED EXIT DEVICES

1000

250

5

250

All dimensions in mm All dimensions in

Setting the Standard in Access Control

80

ADDITIONAL EQUIPMENT

S P-2 Call Point Protector • Polycarbonate construction • Surface mount • Can retrofit over existing device • Red and green covers supplied • Built-in sounder

SPEC I F I CAT ION • Protective cover helps prevent malicious or accidental false fire alarms • Three year guarantee against breakage

• Operating temperature: -40 ~ 49°C (-40 to 120°F) . • Break seal option for added security.

• Available with or without a 96dB integral sounder powered by a 3V lithium battery.

Made with FlippingBook - Online catalogs